<?xml version="1.0" encoding="UTF-8"?>
<mods xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns="http://www.loc.gov/mods/v3" version="3.1" xsi:schemaLocation="http://www.loc.gov/mods/v3 http://www.loc.gov/standards/mods/v3/mods-3-1.xsd">
  <titleInfo>
    <title>Energy conservation in the Petroleum Authority of Thailand (PTT) office building, Bangkok</title>
  </titleInfo>
  <name type="personal">
    <namePart>Shrestha, Rabindra Bahadur</namePart>
    <role>
      <roleTerm authority="marcrelator" type="text">creator</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Surapong Chiraratananon</namePart>
    <role>
      <roleTerm type="text">Chairperson</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Mohanty, B.</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Shrestha, Ram M.</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="corporate">
    <namePart>The Commission of The European Communities</namePart>
    <role>
      <roleTerm type="text">Scholarship Donor</roleTerm>
    </role>
  </name>
  <typeOfResource>text</typeOfResource>
  <genre authority="marc">series</genre>
  <genre authority="marc">technical report</genre>
  <originInfo>
    <place>
      <placeTerm type="code" authority="marccountry">th</placeTerm>
    </place>
    <place>
      <placeTerm type="text">Bangkok</placeTerm>
    </place>
    <publisher>Asian Institute of Technology</publisher>
    <dateIssued>1990</dateIssued>
    <issuance>continuing</issuance>
  </originInfo>
  <language>
    <languageTerm authority="iso639-2b" type="code">eng</languageTerm>
  </language>
  <physicalDescription>
    <extent>135 leaves</extent>
  </physicalDescription>
  <abstract>A study on energy uses in the Petroleum a u thority of Thai lan d (PTT ) Office Building was condu cted. Energy Audit of various  system such as electrical system, air conditioning system were  carried out.  In 1989 the total energy consumption of the Office Building  was about 60240 00 kWH and costed 11.98 million baht. A detail  electri cal measu rement of different feeders were made. The break  down of electrical energy usage in various energy systems are  presented. The percentage of electrical energy contributed by Air  conditioni ng system, Lighting , Lifts , Miscellaneous were 61.39% ,  23.34%, 6.36% and 8.92% respectively .  The electrical energy usage indices and cost effectiveness  are presented to compare the effectiveness of the energy usage.  The average monthly electrical indices are 16.90 kWH/m2 and 33 . 60  bah t /m 2 respectively. The power indices for Air conditioning  system and Lighting are 39.84 W/m 2 and 12.55 W/m2 respectively .  The opportu nities for energy conservation in power and  thermal energy systems are identified , analyzed and recommended.  The monetary saving d u e to reduction of peak demand is  233580 baht per year . The energy saving from reduction of demand  is 134550 baht per year. From the redistribution of Transformer  the saving will be 38261 baht per year. From energy conservation  in lighting system the saving is 622077 bah t per year. A detailed  simulation work of building energy system were carried out. From  the simulation work the result shows that the external heat gain  is the major source of cooling load wh i ch represents 65 . 1% ,  I n filtration 15.3% , Equipment 5.4%, people 7 . 3% and Lighting 6 . 9%  respectively. To reduce the cooling load using protective polyes ter films in the window wi ll save 438126 baht per year . Also  increasing the thermostat set point to 75°F will save 536406 baht  per year.</abstract>
  <note>A Research Study Submitted in Partial fulfilment of the  requirement for the degree of Master of Engineering, School of Environment, Resources and Development</note>
  <note>Research Studies Project Report (M. Eng.) - Asian Institute of Technology, 1990</note>
  <subject authority="lcsh">
    <topic>Buildings</topic>
    <topic>Thailand</topic>
    <topic>Bangkok</topic>
    <topic>Energy conservation</topic>
  </subject>
  <relatedItem type="series">
    <titleInfo>
      <title>Research studies project report ; no. ET-90-2</title>
    </titleInfo>
    <name type="corporate">
      <namePart>Asian Institute of Technology.</namePart>
      <namePart/>
    </name>
  </relatedItem>
  <identifier type="uri">http://203.159.5.9/ait-thesis/detail.php?q=B18164</identifier>
  <location>
    <url displayLabel="Full-Text">http://203.159.5.9/ait-thesis/detail.php?q=B18164</url>
  </location>
  <recordInfo>
    <recordCreationDate encoding="marc">271198</recordCreationDate>
    <recordChangeDate encoding="iso8601">20260818095803.0</recordChangeDate>
  </recordInfo>
</mods>