<?xml version="1.0" encoding="UTF-8"?>
<mods xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns="http://www.loc.gov/mods/v3" version="3.1" xsi:schemaLocation="http://www.loc.gov/mods/v3 http://www.loc.gov/standards/mods/v3/mods-3-1.xsd">
  <titleInfo>
    <title>Experimental monitoring and computer simulation of a solar air-conditioning system</title>
  </titleInfo>
  <name type="personal">
    <namePart>Rao, Malla Raghava</namePart>
    <role>
      <roleTerm authority="marcrelator" type="text">creator</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Reddy, T. A.</namePart>
    <role>
      <roleTerm type="text">Chairperson</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Exell, Robert H.B.</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Huynh, Ngoc Phien</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="corporate">
    <namePart>Canadian International Development Authority</namePart>
    <role>
      <roleTerm type="text">Scholarship Donor</roleTerm>
    </role>
  </name>
  <typeOfResource>text</typeOfResource>
  <originInfo>
    <place>
      <placeTerm type="code" authority="marccountry">th</placeTerm>
    </place>
    <place>
      <placeTerm type="text">Bangkok</placeTerm>
    </place>
    <publisher>Asian Institute of Technology</publisher>
    <dateIssued>1985</dateIssued>
    <issuance>monographic</issuance>
  </originInfo>
  <language>
    <languageTerm authority="iso639-2b" type="code">eng</languageTerm>
  </language>
  <physicalDescription>
    <extent>136 p.</extent>
  </physicalDescription>
  <abstract>The actual performance of a 2 ton YAZAKI WFC600S solar  absorption air-conditioning system was monitored by setting up the necessary instrumentation and recording the data on  cassette tapes using two Campbell CR21 microloggers . Programs were written to retrieve and process this recorded raw data  which was then analyzed in order to study the system  performance. Conclusions are drawn and recommendations made in order to ameliorate the system performance . It has been observed that the chiller is very much undersized for the  intended load and also that there could be an improvement of system performance by minor variations in control and  operational strategy.  A detailed simulation program was also developed which  models the radiation, collector system, building load a nd the  chiller unit while accounting for hysteresis and cycling  effects . The simulation assumes a quasi steady state over a 5  minute simulation time step. The simulation program was  validated with measured data over a few days. In order to  determine the long term performance of the system , the program was run for the entire year and a value of 34.3% f or the  annual solar fraction was obtained.  Programs were developed in order to simulate the system  performance using simplified simulation methods like the o-f  Chart, TMD and MIRA methods. These resulted in annual solar  fractions of 0. 3500, 0.4163 and 0.3562  respectively which are  in accordance wit h the detailed simulations indicating the  validity of these procedures to air-conditioning systems and  also that a high amount of accuracy is achievable by a judicious choice o f an appropriate s1mplitied design method. This procedure would save a lot of resources on program  development and computing time.</abstract>
  <note>A thesis submitted in partial fulfillment of requirements for the degree of Master of Engineering, School of Environment, Resources and Development</note>
  <note>Thesis (M.Eng.) - Asian Institute of Technology, 1985</note>
  <subject authority="lcsh">
    <topic>Solar air conditioning</topic>
    <topic>Simulation methods</topic>
  </subject>
  <relatedItem type="series">
    <titleInfo>
      <title>Thesis ; no. ET-85-6</title>
    </titleInfo>
    <name type="corporate">
      <namePart>Asian Institute of Technology.</namePart>
      <namePart/>
    </name>
  </relatedItem>
  <identifier type="uri">http://203.159.5.9/ait-thesis/detail.php?q=B19988</identifier>
  <location>
    <url displayLabel="Full-Text">http://203.159.5.9/ait-thesis/detail.php?q=B19988</url>
  </location>
  <recordInfo>
    <recordCreationDate encoding="marc">280998</recordCreationDate>
    <recordChangeDate encoding="iso8601">20260818113048.0</recordChangeDate>
  </recordInfo>
</mods>