    <title>feasibility of improved air-conditioning and thermal energy storage in spinning industry</title>
  </titleInfo>
  <name type="personal">
    <namePart>Tian, Wei</namePart>
    <role>
      <roleTerm authority="marcrelator" type="text">creator</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Surapong Chiraratananon</namePart>
    <role>
      <roleTerm type="text">Chairperson</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Mora, J.C.</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Bhattacharya, Sribas C.</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="corporate">
    <namePart>SEC ( State Education Commissi on People' s  Republic of China )</namePart>
    <role>
      <roleTerm type="text">Scholarship Donor </roleTerm>
    </role>
  </name>
  <typeOfResource>text</typeOfResource>
  <originInfo>
    <place>
      <placeTerm type="code" authority="marccountry">th</placeTerm>
    </place>
    <place>
      <placeTerm type="text">Bangkok</placeTerm>
    </place>
    <publisher>Asian Institute of Technology</publisher>
    <dateIssued>1992</dateIssued>
    <issuance>continuing</issuance>
  </originInfo>
  <language>
    <languageTerm authority="iso639-2b" type="code">eng</languageTerm>
  </language>
  <physicalDescription>
    <extent>61 leaves : ill.</extent>
  </physicalDescription>
  <abstract>An essential requirement in the spinning process and part of  the weaving process in the textile industry is the exact control of  humidity in the production environment. In hot, humid climate the  energy intensive air-conditioning equipments used with air washer  for the purpose causes an additional 40% of electricity consumption  on top of that required for manufacturing.  The existing design of the control for the air psychrometrics  is based on a CLOSED air loop. There is a potential for substantial  electricity saving from the use of an OPEN air loop in the order of  18% of that required for the air-conditioning system.  It is perceived that there is a good potential for electricity  cost saving through the use of thermal energy storage under a Time of-Day (TOD) electrical tariff structure.  This study investigates mainly the potential of saving  electricity cost in application of OPEN air loop and in use of ice  and chilled water storage. The study includes physical experiment  with a simulator of air washer system, and computer s i mulation of  air washer with OPEN air loop under Bangkok's weather condition.  The OPEN air loop operation will save electricity energy, but  thermal energy storage reduces demand charge.  The economic evaluation of ice and chilled water storage were  taken under the criteria of PayBack Period, Net Present Value and  Internal Rate of Return. It was found that cool storage is  economically favorable and in combination with OPEN air loop  operation can be very attractive. </abstract>
  <note>A thesis submitted in partial fulfillment of the requirement for the degree of Master of Science</note>
  <note>Thesis (M.Sc.) - Asian Institute of Technology</note>
  <subject authority="lcsh">
    <topic>Heat storage</topic>
  </subject>
  <relatedItem type="series">
    <titleInfo>
      <title>Thesis ; no. ET-92-22</title>
    </titleInfo>
    <name type="corporate">
      <namePart>Asian Institute of Technology.</namePart>
      <namePart/>
    </name>
  </relatedItem>
  <identifier type="uri">http://203.159.5.9/ait-thesis/detail.php?q=B16281</identifier>
  <location>
    <url displayLabel="Full-Text">http://203.159.5.9/ait-thesis/detail.php?q=B16281</url>
  </location>
  <recordInfo>
    <recordCreationDate encoding="marc">290998</recordCreationDate>
    <recordChangeDate encoding="iso8601">20260818113528.0</recordChangeDate>
  </recordInfo>
</mods>