<?xml version="1.0" encoding="UTF-8"?>
<mods xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns="http://www.loc.gov/mods/v3" version="3.1" xsi:schemaLocation="http://www.loc.gov/mods/v3 http://www.loc.gov/standards/mods/v3/mods-3-1.xsd">
  <titleInfo>
    <title>Application of a filter press to a sludge dewatering process in the Bangkhen water treatment plant</title>
  </titleInfo>
  <name type="personal">
    <namePart>Sopin Paethong</namePart>
    <role>
      <roleTerm authority="marcrelator" type="text">creator</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Takizawa, S.</namePart>
    <role>
      <roleTerm type="text">Chairperson</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Visvanathan, C.</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="personal">
    <namePart>Samorn Muttamara</namePart>
    <role>
      <roleTerm type="text">Examination Committee</roleTerm>
    </role>
  </name>
  <name type="corporate">
    <namePart>Metropolitan Waterworks Authority (MWA)</namePart>
    <role>
      <roleTerm type="text">Scholarship donor</roleTerm>
    </role>
  </name>
  <typeOfResource>text</typeOfResource>
  <originInfo>
    <place>
      <placeTerm type="code" authority="marccountry">th</placeTerm>
    </place>
    <place>
      <placeTerm type="text">Bangkok</placeTerm>
    </place>
    <publisher>Asian Institute of Technology</publisher>
    <dateIssued>1998</dateIssued>
    <issuance>monographic</issuance>
  </originInfo>
  <language>
    <languageTerm authority="iso639-2b" type="code">eng</languageTerm>
  </language>
  <physicalDescription>
    <extent>93 leaves</extent>
  </physicalDescription>
  <abstract>This research study emphasized mechanical dewatering characteristics and attempted to  investigate the use of filter press in Bangken Water Treatment Plant because it was anticipated  that in the not-too-distant future the filter press would be considered. Although previous  systems are generally not economically feasible for most treatment plants, improvements in  technology and adjustments in materials and system costs may make them more attractive in  the future.  The specific resistance of the conditioned sludge and CST are determined. They are found that  the addition of optimum dosage of chemicals improve the filterability of sludge to a high  degree, in which the specific resistance of the sludge is decrease from an average of 6.53E+ 11  m/kg to7.48E+10 m/kg. The figure revealed the optimum dosage of Ze Tag 63, anionic  polymer to be 0.08% DS sludge.  A comparison between combination of chemical conditioners to apply in filter pressing  operation indicate that by using anionic polymer with lime in place of cationic would fall in  CST value of 10.7 s, however, the cost of lime and anionic polymer might be higher than that  of cationic polymer for the same degree of conditioning.</abstract>
  <note>A research study submitted in partial fulfillment of the requirements for the degree of Master  of Science, School of Environment, Resources and Development </note>
  <note>Thesis (M.Sc.) - Asian Institute of Technology, 1998</note>
  <subject authority="lcsh">
    <topic>Water</topic>
    <topic>Purification</topic>
    <topic>Filtration</topic>
  </subject>
  <subject authority="lcsh">
    <topic>Sewage sludge</topic>
    <topic>Drying</topic>
  </subject>
  <relatedItem type="series">
    <titleInfo>
      <title>Thesis ; no. EV-98-26</title>
    </titleInfo>
    <name type="corporate">
      <namePart>Asian Institute of Technology.</namePart>
      <namePart/>
    </name>
  </relatedItem>
  <identifier type="uri">http://203.159.5.9/ait-thesis/detail.php?q=B12746</identifier>
  <location>
    <url displayLabel="Full-Text">http://203.159.5.9/ait-thesis/detail.php?q=B12746</url>
  </location>
  <recordInfo>
    <recordCreationDate encoding="marc">011298</recordCreationDate>
    <recordChangeDate encoding="iso8601">20260817162825.0</recordChangeDate>
  </recordInfo>
</mods>